ADAM-4060
Relay Output Module


 

Introduction
Applications
Specifications
Ordering Information
 
Introduction Return to top of page

Simple configuration, easy programming and supported by major DA & C packages - these are just a few reasons to use Advantech's ADAM 4000 modules.

The ADAM-4060 Relay Module is controlled remotely and stores its configuration data in EEPROM. It provides four relay channels, two of Form A and two of Form C. This module is excellent for On/Off control or low-power applications.

You can use any high-level language with ASCII-based string functions (such as C, Pascal or BASIC) to communicate with ADAM modules or process their data. For example, the command and response for an analog input module would be: COMMAND: #5, RESPONSE: > 4.834. This command requests the data stored by the module with address 05 (Hex). The module responds with the value 4.834 V.

ADAM's built in checksum feature ensures data integrity by detecting communication errors. This feature adds two checksum characters to every command or response string that enable you to verify that the message received is exactly the same as the message sent.

Easy-to-use menu-driven utility software make configuration and calibration a snap. Its terminal emulation program lets you easily read from and write to ADAM modules. Writing application programs with this software (GENIE 2.0) is simple, you can learn the basics in just a few minutes.

 

  • On/Off control
  • Low-power switching

Communication

  • RS-485 (2-wire) to host
  • Speeds: 1200, 2400, 4800, 9600, 19200 bps
  • Max. communication distance: 4000feet (1.2Km)
  • Power and communication LED indicator
  • ASCII command/response protocol
  • Communication error checking with checksum
  • Asynchronous data format: 1 start bit, 8 data bits, 1 stop bit, no parity
  • Up to 256 multidrop modules per serial port
  • On-line module insertion and removal
  • Transient suppression on RS-485 communication lines

Power Requirements

  • Unregulated 10 30 VDC
  • Protected against power reversal

Mechanical

  • Case: ABC with captive mounting hardware
  • Plug-in screw terminal block:
    Accepts 0.5 mm² to 2.5 mm²
    1-#12 or 2-#14 to #22 AWG

Environment

  • Operating temperature: 14 to 158ºF (-1000 to 70ºC)
  • EMI: Meets FCC Class A
  • Storage temperature: -13 to 185ºf (-25 to 85ºC)
  • Humidity: 5 to 95%, non-condensing

Relay Output Return to top of page

  • Channels: 4-channel relay, two form A and two form C

Characteristics

  • Contact rating:
    AC: 125 V @ 0.6 A; 250 V @ 0.3 A
    DC: 30 V @ 2 A; 110 V @ 0.6 A
  • Breakdown voltage: 500 VAC (50/60 Hz)
  • Relay on time (typical): 3 msec
  • Relay off time (typical): 1 msec
  • Total switching time: 10 msec
  • Insulation resistance: 1000 M OHM minimum at 500 VDC

Power

  • Power requirements: 10 to 30 V (non-regulated)
  • Power consumption: 0.8 W

 

 

ADAM-4060 

Relay Output Module

Q. What is the relay life on the ADAM-4060?
A. The lifetime for the relay in the ADAM-4060 is different with different operating conditions.
  • Mechanical (600cpm): 100,000,000 switches
  • Electrical: 2A 30V 500,000
  • 1A 30V 2,000,000 (8/6/96)
Return to top of pageReturn to top of page

Ordering Information

Specifications

Applications

 
 
 
USA Office

Tel:1.877.902.2979-1.425.223.4311
Fax:1.877.329.4324
Address: 1480 Gulf Road, Suite 837,
PO Box 1364
Point Roberts, WA 98281

Western Canada - Vancouver BC

Tel:1.800.663.6001 or 1.604.925.6150
Fax:1.604.925.6170
Address: 2454 Haywood Ave
West Vancouver, BC V7V 1Y1

Eastern Canada - Markham, Ontario

Tel:1.800.465.0164 or 1.905.513.7027
Fax:1.877.329.4324