Log In

 

48 Years in Business

 

Follow us on Facebook for all the latest news, updates and promotions

 

Credit Cards Accepted

 

Aurora Probability
Northern US States and 
Southern Canadian States.
 

For more precise predictions
go to

https://www.swpc.noaa.gov

Auroral forecast from AuroraWatch.ca

ADAM-4052
Isolated Digital Input Module


 

Introduction
Applications
Specifications
Ordering Information
 
Introduction Return to top of page

Simple configuration, easy programming and supported by major DA & C packages - these are just a few reasons to use Advantech's ADAM 4000 modules.

The ADAM-4052 provides eight digital input channels: six fully independent isolated channels and two isolated channels with a common ground. All have 5000RMS isolation to prevent ground loop effects and limit the chance of damage from power surges on the input lines.

You can use any high-level language with ASCII-based string functions (such as C, Pascal or BASIC) to communicate with ADAM modules or process their data. For example, the command and response for an analog input module would be: COMMAND: #5, RESPONSE: > 4.834. This command requests the data stored by the module with address 05 (Hex). The module responds with the value 4.834 V.

ADAM's built in checksum feature ensures data integrity by detecting communication errors. This feature adds two checksum characters to every command or response string that enable you to verify that the message received is exactly the same as the message sent.

Easy-to-use menu-driven utility software make configuration and calibration a snap. Its terminal emulation program lets you easily read from and write to ADAM modules. Writing application programs with this software (ADAMView) is simple, you can learn the basics in just a few minutes.

Applications

 

  •   Under Construction

Specifications

Communication

  • RS-485 (2-wire) to host
  • Speeds: 1200, 2400, 4800, 9600, 19200 bps
  • Max. communication distance: 4000feet (1.2Km)
  • Power and communication LED indicator
  • ASCII command/response protocol
  • Communication error checking with checksum
  • Asynchronous data format: 1 start bit, 8 data bits, 1 stop bit, no parity
  • Up to 256 multidrop modules per serial port
  • On-line module insertion and removal
  • Transient suppression on RS-485 communication lines

Power Requirements

  • Unregulated 10 30 VDC
  • Protected against power reversal

Mechanical

  • Case: ABC with captive mounting hardware
  • Plug-in screw terminal block:
    Accepts 0.5 mm² to 2.5 mm²
    1-#12 or 2-#14 to #22 AWG

Environment Return to top of page

  • Operating temperature: 14 to 158ºF (-1000 to 70ºC)
  • EMI: Meets FCC Class A
  • Storage temperature: -13 to 185ºf (-25 to 85ºC)
  • Humidity: 5 to 95%, non-condensing

Digital Input

  • Channels: 8
    Six fully independent isolated channels,
    two isolated channels with common ground
  • Digital input level:
    Logic level 0: 1 V max.
    Logic level 1: 3.5 V ~ 30 V
  • Isolation voltage: 5000 Vrms
  • Input resistance: 3 K OHMs/0.5W

Power

  • Power requirements: 10 to 30 V (non-regulated)
  • Power consumption: 0.4 W

 

Ordering Information

 

ADAM-4052

Isolated Digital Input Module
Return to top of pageReturn to top of page
 
 
 
USA Office

Tel:1.877.902.2979-1.425.223.4311
Fax:1.877.329.4324
Address: 1480 Gulf Road, Suite 837,
PO Box 1364
Point Roberts, WA 98281

Western Canada - Vancouver BC

Tel:1.800.663.6001 or 1.604.925.6150
Fax:1.604.925.6170
Address: 2454 Haywood Ave
West Vancouver, BC V7V 1Y1

Eastern Canada - Markham, Ontario

Tel:1.800.465.0164 or 1.905.513.7027
Fax:1.877.329.4324