ADAM-4050
Digital I/O Module


 

Introduction
Applications
Specifications
Ordering Information
 
Introduction Return to top of page

Simple configuration, easy programming and supported by major DA & C packages - these are just a few reasons to use Advantech's ADAM 4000 modules.

The analog input module's two digital output channels are open-collector transistor switches that you can control from the host computer. By switching solid state relay the output channels can control heaters, pumps and other power equipment. The module can use its one digital input channel to sense the state of a remote digital signal

Analog input modules include high and low alarm signaling with remotely configurable limit values. After every A/D conversion, the digital value is compared with the high and low limit. The module can change the state of a digital output depending on the result of this comparison. This lets it perform On/Off control of a device independent of the host PC.

The on-board event counter can count up to 65,535 transitions occurring on the digital input. The counter can be read and cleared by the host computer. the counter can be used in production line applications to keep a record of repetitive operations.

The ADAM-4050 features seven digital input channels and eight digital output channels. The outputs are open-collector transistor switches that you can control from the host computer. You can also use the switches to control solid-state relays, which in turn can control heaters, pumps or other power equipment. The host computer can use the module's digital inputs to determine the state of limit or safety switches or remote digital signals.

Easy-to-use menu-driven utility software make configuration and calibration a snap. Its terminal emulation program lets you easily read from and write to ADAM modules. Writing application programs with this software (GENIE 2.0) is simple, you can learn the basics in just a few minutes.

Applications

 

  •  Control heaters, pumps or other power equipment

Specifications

Communication

  • RS-485 (2-wire) to host
  • Speeds: 1200, 2400, 4800, 9600, 19200 bps
  • Max. communication distance: 4000feet (1.2Km)
  • Power and communication LED indicator
  • ASCII command/response protocol
  • Communication error checking with checksum
  • Asynchronous data format: 1 start bit, 8 data bits, 1 stop bit, no parity
  • Up to 256 multidrop modules per serial port
  • On-line module insertion and removal
  • Transient suppression on RS-485 communication lines

Power Requirements

  • Unregulated 10 30 VDC
  • Protected against power reversal

Mechanical

  • Case: ABC with captive mounting hardware
  • Plug-in screw terminal block:
    Accepts 0.5 mm² to 2.5 mm²
    1-#12 or 2-#14 to #22 AWG

Environment

  • Operating temperature: 14 to 158ºF (-1000 to 70ºC)
  • EMI: Meets FCC Class A
  • Storage temperature: -13 to 185ºf (-25 to 85ºC)
  • Humidity: 5 to 95%, non-condensing

Digital Input Return to top of page

  • Channels: 7
  • Logic level 0: 1 V max.
  • Logic level 1: 3.5 V ~ 30 V
  • Pull up current: 0.5 mA, 10 K OHM resistor to 5V

Digital Output

  • Channels: 8
  • Open collector to 30 V, 30 mA max. load
  • Power dissipation: 300 mW

Power

  • Power requirements: 10 to 30 V (non-regulated)
  • Power consumption: 0.4 W

 

Ordering Information

 

ADAM-4050

Digital I/O Module (7DI, 8DO)
Return to top of pageReturn to top of page
 
 
 
USA Office

Tel:1.877.902.2979-1.425.223.4311
Fax:1.877.329.4324
Address: 1480 Gulf Road, Suite 837,
PO Box 1364
Point Roberts, WA 98281

Western Canada - Vancouver BC

Tel:1.800.663.6001 or 1.604.925.6150
Fax:1.604.925.6170
Address: 2454 Haywood Ave
West Vancouver, BC V7V 1Y1

Eastern Canada - Markham, Ontario

Tel:1.800.465.0164 or 1.905.513.7027
Fax:1.877.329.4324