ADAM-4018m
8-Channel Analog Input Data Logger


 

Introduction
Applications
Specifications
Ordering Information
Introduction Return to top of page

Simple configuration, easy programming and supported by major DA & C packages - these are just a few reasons to use Advantech's ADAM 4000 modules.

The ADAM-4018M provides the same functions as the 4018 modules but can also store up to 10,000 signal samples in it's 32 KB Flash memory. It has user definable sample intervals from 1 second to 18 hours. When using the Event Logging Mode data is recorded when an input exceeds a predetermined high or low alarm condition. Stored data can be read by the host computer at any time via an RS-485 network. The Flash ROM also provides a backup for read data for retrieval in the event of a power failure or removal from the system when interrogated.

You can use any high-level language with ASCII-based string functions (such as C, Pascal or BASIC) to communicate with ADAM modules or process their data. For example, the command and response for an analog input module would be: COMMAND: #5, RESPONSE: > 4.834. This command requests the data stored by the module with address 05 (Hex). The module responds with the value 4.834 V.

ADAM's built in checksum feature ensures data integrity by detecting communication errors. This feature adds two checksum characters to every command or response string that enable you to verify that the message received is exactly the same as the message sent.

Easy-to-use menu-driven utility software make configuration and calibration a snap. Its terminal emulation program lets you easily read from and write to ADAM modules. Writing application programs with this software (GENIE 2.0) is simple, you can learn the basics in just a few minutes.

ADAM-4018M Datasheet

Applications Return to top of page

  •   Under Construction

Specifications Return to top of page

Communication

  • RS-485 (2-wire) to host
  • Speeds: 1200, 2400, 4800, 9600, 19200 bps
  • Max. communication distance: 4000feet (1.2Km)
  • Power and communication LED indicator
  • ASCII command/response protocol
  • Communication error checking with checksum
  • Asynchronous data format: 1 start bit, 8 data bits, 1 stop bit, no parity
  • Up to 256 multidrop modules per serial port
  • On-line module insertion and removal
  • Transient suppression on RS-485 communication lines

Power Requirements

  • Unregulated 10 30 VDC
  • Protected against power reversal

Mechanical

  • Case: ABC with captive mounting hardware
  • Plug-in screw terminal block:
    Accepts 0.5 mm² to 2.5 mm²
    1-#12 or 2-#14 to #22 AWG

Environment

  • Operating temperature: 14 to 158ºF (-1000 to 70ºC)
  • EMI: Meets FCC Class A
  • Storage temperature: -13 to 185ºf (-25 to 85ºC)
  • Humidity: 5 to 95%, non-condensing

Analog Input Return to top of page

  • Channels: Six differential, two single-ended
  • Input type: Thermocouple, mV, V or mA
  • Input range: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA
  • TC Type: J, K, T, E, R, S, and B

Characteristics

  • Isolation voltage: 500 VDC
  • Sampling rate: 10 samples/sec. (total)
  • Bandwidth: 13.1 Hz
  • Accuracy: ±0.1% or better
  • Zero drift: ±0.3 µV/°C
  • Span drift: ±25 ppm/°C
  • CMR @ 50/60 Hz: 92 dB min.

Storage

  • Storage Capacity (32 KB Flash Memory): 10,000 samples (total)
  • Storage mode: Write to end of memory
  • Logging mode: Internal log or event log (high/Low)
  • Sampling interval: 2 sec. to 18 hours

Power

  • Power requirements: 10 to 30 V (non-regulated)
  • Power consumption: 1.2 W

Ordering Information Return to top of page

ADAM-4018M 
8-Channel Analog Input Data Logger Module mV, mA, TC
 
 
 
USA Office

Tel:1.877.902.2979-1.425.223.4311
Fax:1.877.329.4324
Address: 1480 Gulf Road, Suite 837,
PO Box 1364
Point Roberts, WA 98281

Western Canada - Vancouver BC

Tel:1.800.663.6001 or 1.604.925.6150
Fax:1.604.925.6170
Address: 2454 Haywood Ave
West Vancouver, BC V7V 1Y1

Eastern Canada - Markham, Ontario

Tel:1.800.465.0164 or 1.905.513.7027
Fax:1.877.329.4324